clint MULTIPOWER.png

CHA/K/A/WP 726-P÷24012-P

A CLASS energy efficiency aircooled reversible Heat Pumps with axial fans, Scroll compressors and plate exchanger

CALDO_FREDDO_MIDY.png COMPRESSORE_SCROLL111.png ASSIALE11.png SCAMBIATORE_PIASTRE11.png _icon_A_CLASS_2018_heating.png R410A1.png icon_refrigerant_R452B.png icon_refrigerant_R454B.png

The CHA/K/A/WP 726-P÷24012-P reversible Heat Pumps are characterized by A CLASS energy efficiency.
The units are characterized by multi-compressor design on double cooling circuit, to reach high energy performances, reduction of current at start-up, elimination of inertial tanks and excellent silent functioning. The use of components built in large series makes them highly reliable and the management of a high number of compressors allows increased life span with reduction of machine stopping risks and easier maintenance operations. A wide range of accessories, factory fitted or supplied separately, complete the outstanding versatility and functionality of the series.
Are available as option the new EC Inverter fans with high available static pressure and efficiency.
The units are designed for hot water production up to 55°C.
The units are compliant to the ErP Regulation.
 
On request, units can be supplied with R452B or R454B refrigerant.

Versions

  • CHA/K/A/WP - Reversible Heat Pump
  • CHA/K/A/WP/SSL - Super silenced reversible Heat Pump

Power range

  • 194-671 kW
  • 55.0-191 Ton

Features

  • Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
  • Scroll compressors with oil sight glass, internal overheat protection and crankcase heater.
  • Axial fans directly coupled to an electric motor with external rotor.
  • Condenser made of copper tubes and aluminium finned coils.
  • Evaporator AISI 316 stainless steel braze welded plates type with two independent circuits on the refrigerant side and one on the water side, complete with water differential pressure switch. On the units it is always installed an antifreeze heater.
  • Cooling circuit shut-off valve on liquid line in 1048-P÷24012-P models.
  • Electronic expansion valve.
  • Electronic high and low pressure gauges.
  • R410A refrigerant. On request R452B or R454B refrigerant.
  • Electrical board includes: main switch with door safety interlock, fuses or magnetothermic switches, thermal protection relays for compressors and thermocontacts for fans.
  • Functioning in heating mode with outside air temperature down to -15 °C.
  • Microprocessor control and regulation system.

Factory fitted accessories

  • IM Automatic circuit breakers
  • SL Unit silencement
  • RFM Cooling circuit shut-off valve on discharge line
  • CT Condensing control down to 0 °C
  • CC Condensing control down to -20 °C
  • BT Low water temperature kit
  • EC EC Inverter fans
  • ECH EC Inverter fans with high available static pressure
  • DS Desuperheater
  • RT Total heat recovery
  • TX Coil with pre-coated fins
  • EW External water connections
  • PS Single circulating pump
  • PSI Inverter single circulating pump
  • PD Double circulating pump
  • PDI Inverter double circulating pump
  • GS Single circulating pump gasket for glycol >30%
  • GD Double circulating pump gaskets for glycol >30%
  • SS Soft start
  • IS Modbus RTU protocol, RS485 serial interface
  • IST Modbus TCP/IP protocol, Ethernet port
  • ISB BACnet MSTP protocol, RS485 serial interface
  • ISBT BACnet IP protocol, Ethernet port
  • ISS SNMP protocol, Ethernet port
  • IAV Remote set-point, 0-10V signal
  • IAA Remote set-point, 4-20mA signal
  • IAS Remote signal for second set-point activation
  • IDL Demand limit from digital input
  • MN High and low pressure gauges

Loose accessories

  • CR Remote control panel
  • RP Coils protection metallic guards
  • AG Rubber shock absorbers
  • AM Spring shock absorbers
726-P786-P826-P906-P1048-P1128-P1208-P13010-P15010-P16812-P18012-P21012-P24012-P
HeatingHeating capacity (1)kW227256272294342369389420476532566677762
Absorbed power (1)kW66758185102106112125141157169202226
COP (1)3,443,413,363,463,353,483,473,363,383,393,353,353,37
Heating (EN14511)Heating capacity (1)kW228257273295343370390422478533568679764
Absorbed power (1)kW68778387105108115128144160172206230
COP (1)3,353,343,293,393,273,433,393,303,323,333,303,303,32
SCOP (2)3,403,473,403,393,423,393,403,413,373,413,363,383,48
Energy Efficiency (2)%133136133133134133133133132133131132136
CoolingCooling capacity (3)kW194217239259294322339359421475512597671
Absorbed power (3)kW68757885100107113127144162172207241
EER (3)2,852,893,063,052,943,013,002,832,922,932,982,882,78
Cooling (EN14511)Cooling capacity (3)kW193216238258293321338358419474510595669
Absorbed power (3)kW69767986101108114128146163174209243
EER (3)2,802,843,013,002,902,972,962,802,872,912,932,852,75
SEER (4)4,054,064,104,114,074,074,084,354,424,454,554,554,55
Energy Efficiency (4)%159159161161160160160171174175179179179
CompressorQuantity3+33+33+33+34+44+44+45+55+56+66+66+66+6
Refrigerant circuits2222222222222
Capacity steps66668888810101010
EvaporatorWater flowl/s9,2710,3711,4212,3714,0515,3816,2017,1520,1122,6924,4628,5232,06
Pressure dropskPa44554238493741464632373330
Water connectionsDN808080808080808080150150150150
Electrical characteristicsPower supplyV/Ph/Hz400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50
Max. running currentA152166187199224241258274324358391446500
Max. starting currentA276299354367357409426407492525558623678
Unit with pumpPump available static pressurekPa155130205190180185175160130185175160145
Water connectionsDN100100100100100100100100100100100150150
Sound pressureSTD version (5)dB(A)72717172727374747676767677
With SL accessory (5)dB(A)69686869697071717373737374
SSL version (5)dB(A)6565656666676767686970------
WeightsTransport weightkg1954229124092437256728202830301931643702383246604698
Operating weightkg1970231024302460259028502860305032003750388047204770

Dimensions

726-P786-P826-P906-P1048-P1128-P1208-P13010-P15010-P16812-P18012-P21012-P24012-P
LSTDmm2800400040004000400050005000500050006200620072007200
SSLmm40004000500050005000500050005000620062007200------
WSTD/SSLmm2200220022002200220022002200220022002200220022002200
HSTD/SSLmm2100210021002100210021002100210021002100210021002100

Notes

  • 1 Heated water from 40 to 45 °C, ambient air temperature 7 °C d.b./6 °C w.b.
  • 2 Seasonal energy efficiency of heating at low temperature with average climatic conditions. According to EU Regulation n. 813/2013.
  • 3 Chilled water from 12 to 7 °C, ambient air temperature 35 °C.
  • 4 Seasonal energy efficiency of cooling at low temperature. According to EU Regulation n. 2016/2281.
  • 5 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
  • N.B. (1) Weights of SSL version are specified on technical brochure.